Assemblies like this are often found in riser rooms.
Fire sprinkler riser room signage requirements.
Fire riser room signs.
Riser assembly shall have a minimum of 36 inches of clearance around the pipe.
Use indoors or outdoors to provide superior resistance to weather.
7 inches high by 10 inches width with 0 5 inch letter stroke white reflective letters on a red background and shall be permanently attached at normal eye level to the door leading to the fire sprinkler control equipment.
Use vivid labels or signs to equip multiple fire protection systems.
There shall be 36 inches of clearance in front of the fire alarm control panel facp.
Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40ºf 4ºc.
Help personnel and emergency responders easily locate your sprinkler system controls.
Risers are the vertical supply pipes in sprinkler systems as defined by nfpa 13 sec.
One side may be a minimum of 18 inches from a wall.
Access doors for automatic sprinkler system riser rooms and fire pump rooms shall be labeled with an approved sign.
Fire pump and riser rooms shall be maintained to be no lower than 40 degrees fahrenheit with the heating device permanently installed.
The requirement all sprinkler systems are required to provide a general information sign placed at each system control riser antifreeze loop and auxiliary system control valve.
The minimum size of the equipment room shall allow adequate firefighter access and mobility with the following minimum clearance requirements.
Permanently installed artificial illumination shall be provided in the automatic sprinkler system riser rooms and fire pump rooms.
Most fire sprinkler system valves must be identified with metal or rigid plastic signs section 6 6 4 of nfpa 13 stipulates sign requirements for all control drain venting and test connection valves while section 8 16 1 1 expands on the guidance for control valves.
Heating units shall be permanently installed.
Fire department sprinkler signs pipe markers and nfpa signs for your facility s fire safety plan.
Mount on doors or hang from riser systems with a chain.
Fire sprinkler pipe markers.
Change significance this code change adds additional criteria to.
Fast shipping direct from usa manufacturer.
The letterings hall be in contrasting color to the background.
Permanent artificial lighting is now required to be installed by the 2018 ifc ibc.
Quickly identify critical fire riser rooms when you need them the most.
Sprinkler riser room signs are intended to alert emergency response and maintenance crews to the location of fire sprinkler system risers.